Fault Codes | Fault Description | Possible Causes |
---|---|---|
Fault Code F1 | Ignition Failure | Insufficient Inlet Working Gas Pressure At The Appliance |
Flue Problem | ||
Spark Generation Issue | ||
Incorrect Gas Valve Adjustment (Minimum Burner Pressure Set Too Low) | ||
Flame Rectification Issue | ||
Combustion Issue (Poor Flame Picture) | ||
Software Error On The Main PCB Or The User Interface PCB | ||
Fault Code F2 | Air Fault | Fan Fault |
Fan Venturi Blocked | ||
PCB Fault (No Power To The Fan) | ||
Wiring Harness Fault Between The Fan And The Main PCB | ||
The Air Pressure Switch Is Not Switching To The N/O Position When The Fan Is Running | ||
The Air Pressure Switch Jammed In The “Made” Position Prior To The Fan Operation | ||
Fault Code F3 | Air Fault | Fan Fault |
Fan Venturi Blocked | ||
PCB Fault (No Power To The Fan) | ||
Wiring Harness Fault Between The Fan And The Main PCB | ||
The Air Pressure Switch Is Not Switching To The N/O Position When The Fan Is Running | ||
The Air Pressure Switch Jammed In The “Made” Position Prior To The Fan Operation | ||
Fault Code F4 | Flame Sensing Fault | Insufficient Inlet Working Gas Pressure At The Appliance |
Flue Problem | ||
Incorrect Gas Valve Adjustment (Minimum Burner Pressure Set Too Low) | ||
Poor Combustion (Poor Flame Picture) | ||
Flame Sensing Electrode Faulty Or Incorrectly Positioned | ||
Incoming Power Supply Issue (Reverse Polarity, Neutral Fault, Earth Fault) | ||
Software Error On The Main PCB Or The User Interface PCB | ||
Fault Code F5 | Overheat Fault | The Overheat Thermostat Has Activated In The Appliance Due To Poor Circulation (115C) |
Pump Not Running | ||
Appliance Heating Return Filter Blocked | ||
Air Lock Within The Boiler Or The System | ||
Blockage Within The Boiler Or The System | ||
System Design Issue | ||
Insufficient System Bypass | ||
NTC Thermistor Out Of Calibration (Should Read 12Kohms @ 20C) | ||
Harness Fault Between The Overheat Thermostat And The Main PCB | ||
Fault Code F6 | Thermistor Fault | The NTC Thermistor Has Gone Open Circuit (Should Read 12Kohms @ 20C) |
Wiring Harness Fault Or Connection Fault Between Thermistor And The Main PCB |