Fault | Rinnai Error Code Remedy |
---|---|
No burner operation during freeze protection mode | Service Necessary Call (647) 925-1930 |
Power interruption during Bath Fill (Water will not flow when power returns). | Turn off all hot water taps. Press ON/OFF twice. |
Air Supply or Exhaust Blockage | Ensure Rinnai approved venting materials are being used. |
Check that nothing is blocking the flue inlet or exhaust. | |
Check all vent components for proper connections. | |
Ensure vent length is within limits. | |
Ensure condensation collar was installed correctly. | |
Verify dip switches are set properly. | |
Check fan for blockage. | |
No Ignition | Check that the gas is turned on at the water heater, gas meter, or cylinder. |
Ensure gas type and pressure is correct. | |
Ensure gas line, meter, and/or regulator is sized properly. | |
Bleed all air from gas lines. | |
Verify dip switches are set properly. | |
Ensure appliance is properly grounded. | |
Disconnect EZConnect™ or MSA controls to isolate the problem. | |
Ensure igniter is operational. | |
Check igniter wiring harness for damage. | |
Check gas solenoid valves for open or short circuits. | |
Remove burner cover and ensure all burners are properly seated. | |
Remove burner plate and inspect burner surface for condensation or debris. | |
Flame Failure | Check that the gas is turned on at the water heater and gas meter. Check for obstructions in the flue outlet. |
Ensure gas line, meter, and/or regulator is sized properly. | |
Ensure gas type and pressure is correct. | |
Bleed all air from gas lines. | |
Ensure proper Rinnai venting material was installed. | |
Ensure condensation collar was installed properly. | |
Ensure vent length is within limits. | |
Verify dip switches are set properly. | |
Ensure appliance is properly grounded. | |
Disconnect keypad. | |
Disconnect EZConnect™ or MSA controls to isolate the problem. | |
Check power supply for loose connections. | |
Check power supply for proper voltage and voltage drops. | |
Ensure flame rod wire is connected. | |
Check flame rod for carbon build-up. | |
Disconnect and reconnect all wiring harnesses on unit and PC board. | |
Check for DC shorts at components. | |
Check gas solenoid valves for open or short circuits. | |
Remove burner plate and inspect burner surface for condensation or debris. | |
Thermal Fuse | Check gas type of unit and ensure it matches gas type being used. |
Check for restrictions in air flow around unit and vent terminal. | |
Check for low water flow in a circulating system causing short-cycling. | |
Ensure dip switches are set to the proper position. | |
Check for foreign materials in combustion chamber and/or exhaust piping. | |
Check heat exchanger for cracks and/or separations. | |
Check heat exchanger surface for hot spots which indicate blockage due to scale build-up. | |
Refer to instructions in manual for flushing heat exchanger. | |
Measure resistance of safety circuit. | |
Ensure high fire and low fire manifold pressure is correct. | |
Check for improper conversion of product. | |
Over Temperature Warning | Check for restrictions in air flow around unit and vent terminal. |
Check for low water flow in a circulating system causing short-cycling. | |
Check for foreign materials in combustion chamber and/or exhaust piping. | |
Check for clogged heat exchanger. | |
Outgoing Water Temperature Sensor Fault | Check sensor wiring for damage. |
Measure resistance of sensor. | |
Clean sensor of scale build-up. | |
Replace sensor. | |
Heat Exchanger Outgoing Temperature Sensor Fault | Check sensor wiring for damage. |
Measure resistance of sensor. | |
Clean sensor of scale build-up. | |
Replace sensor. | |
Combustion Air Temperature Sensor Fault | Check for restrictions in air flow around unit and vent terminal. |
Check sensor wiring for damage. | |
Measure resistance of sensor. | |
Clean sensor of scale build-up. | |
Ensure fan blade is tight on motor shaft and is in good condition. | |
Replace sensor. | |
Modulating Solenoid Valve Signal Abnormal | Check modulating gas solenoid valve wiring harness for loose or damaged terminals. |
Measure resistance of valve coil. | |
Combustion Fan Failure | Ensure fan will turn freely. |
Check wiring harness to motor for damaged and/or loose connections. | |
Measure resistance of motor winding. | |
Water Flow Control Fault | The water flow control valve has failed to close during the bath fill function. Immediately turn off the water and discontinue the bath fill function. |
Contact a qualified or licensed contractor to service the appliance. | |
Toronto and Area (647) 925-1930 | |
SV0, SV1, SV2, and SV3 | Check wiring harness to all solenoids for damage and/or loose connections. |
Solenoid Valve Circuit Fault | Measure resistance of each solenoid valve coil. |
Flame Sensing Device Fault | Ensure flame rod is touching flame when unit fires. |
Check all wiring to flame rod for damage. | |
Remove flame rod and check for carbon build-up; clean with sand paper. | |
Check inside burner chamber for any foreign material blocking flame at flame rod. | |
Measure micro amp output of sensor circuit with flame present. | |
Replace flame rod. | |
Scale Build-up in Heat Exchanger (when checking maintenance code history, “00” is substituted for “LC”) | Flush heat exchanger. |
99$ Toronto and area flush (647) 925-1930 | |
Replace heat exchanger. | |
NOTE: The LC code is the only error code that will allow the unit to keep running. The | |
display will alternate between the LC code and the temperature setting. The controller will continue to beep. The LC code will reset if power is turned off and then on. | |
Nothing happens when water flow is activated. | Clean inlet water supply filter. |
On new installations ensure hot and cold water lines are not reversed. | |
Check for bleed over. Isolate unit from building by turning off hot water line to building. | |
Isolate the circulating system if present. Open your pressure relief valve; if water is flowing, there is bleed over in your plumbing. | |
Ensure you have at least the minimum flow rate required to fire unit. | |
Ensure turbine spins freely. | |
Measure the resistance of the water flow control sensor. | |
Check for DC shorts at components. |
Rinnai Tankless Boiler Error Codes
Rinnai Tankless Boiler Error Codes